600V Duplex Conductor URD Cable
The Duplex Aluminum 600V Single Conductor URD Cable is designed for using in power secondary distribution circuits, which is also called copper urd cable. It is used in wet and dry areas and installed in duct or direct burial applications. The maximum working temperature is limited to 90°C. The voltage rating is 600 volts. This cable can also be provided pre-pulled into duct as an alternative. It is made of crosslinked polyethylene insulation and concentric stranded or compressed 1350-H19 series aluminum conductor. Cable surface printed with the necessary content, neutral phase identified with triple yellow strips, or black neutral if desired.
600V Duplex Conductor URD Cable Features
Specifications of 600V Duplex Conductor URD Cable
Code Name | Phase Conductor | Neutral | Single Phase Conductor (in) | Outside diameter (in) | Weight Per 1000ft (lbls) | Ampacity | |||||
---|---|---|---|---|---|---|---|---|---|---|---|
Size AWG | Strand | Insulation Thickness (mls) | Size AWG | Strand | Insulation Thickness (mls) | Direct Burial | In Duct | ||||
Bard | 8 | 7/w | 60 | 8 | 7/w | 60 | .262 | .524 | 76 | 70 | 70 |
Claflin | 6 | 7/w | 60 | 6 | 7/w | 60 | .299 | .596 | 91 | 95 | 70 |
Delgado | 4 | 7/w | 60 | 4 | 7/w | 60 | .345 | .690 | 129 | 125 | 90 |
Everett | 2 | 7/w | 60 | 2 | 7/w | 60 | .403 | .806 | 189 | 187 | 100 |
Ampacity: 90°C conductor temperature, 20°C ambient temperature. RHO 90. 100% load factor. All Yellow Extruded Stripe, cable is XLP insulation.
To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Packaging: Available in 500 ft.coils 500ft. reels and long lengths.
The above data are approximate and subject to normal manufacturing tolerances.