600V Single Conductor URD Cable

The Aluminum 600V Single Conductor URD Cable is designed for using in power secondary distribution circuits. This urd wire in conduit is used in wet and dry areas and installed in duct or direct burial applications. The maximum working temperature is limited to 90°C. The voltage rating is 600 volts. This cable can also be provided pre-pulled into duct as an alternative. Cable structure is made up by crosslinked polyethylene insulation and concentric stranded or compressed 1350-H19 series aluminum conductor.

+86 13513807403
SHARE:

600V Single Conductor URD Cable Features

Standard
ASTM B-230,B-231 and ICEA S-66-524 ,UL Standard 854 for type USE
Application
Just likecopper urd cable, it can be directly buried or installed in ducts for 600 volt secondary distribution.
Cable in Duct(CIC)
Abrasion Resistant

Specifications of 600V Single Conductor URD Cable

Code NameCond.Size AWG or MCMStrandingInsulation Thickness (mls)Outside Diam (inches)Weight per 1000ft(lbs)Ampacity
Direct BurialIn Duct
ALL ALUMINUM
Princeton67/w60.298459065
Mercer47/w60.3456412085
Clemson27/w60.40393155115
Kenyon119/w80.482122175130
Harvard1/019/w80.522148200150
Yale2/019/w80.566179225170
Tufts3/019/w80.616217250195
Beloit4/019/w80.672265290225
Hofstra25037/w95.748317320250
Gonzaga30037/w95.801371355280
Rutgers35037/w95.851423385305
Emory50037/w95.979579465370
Duke60061/w1101.086701510410
Furman70061/w1101.155804550440
Sewanee75061/w1101.188855580470
Fordham100061/w1101.3371109670545

To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Packaging: Available in 500 ft. coils 1,000ft. reels and long lengths.
The above data are approximate and subject to normal manufacturing tolerances.
Ampacity 90°C conductor temperatures, 20°C ambient temperature. RHO factor 90. 100% load factor for three conductor triplexed, 3 phase operation