600V Single Conductor URD Cable

The Aluminum 600V Single Conductor URD Cable is designed for using in power secondary distribution circuits. This urd wire in conduit is used in wet and dry areas and installed in duct or direct burial applications. The maximum working temperature is limited to 90°C. The voltage rating is 600 volts. This cable can also be provided pre-pulled into duct as an alternative. Cable structure is made up by crosslinked polyethylene insulation and concentric stranded or compressed 1350-H19 series aluminum conductor.

+86 13513807403
SHARE:

600V Single Conductor URD Cable Features

Standard
ASTM B-230,B-231 and ICEA S-66-524 ,UL Standard 854 for type USE
Application
Just likecopper urd cable, it can be directly buried or installed in ducts for 600 volt secondary distribution.
Cable in Duct(CIC)
Abrasion Resistant

Specifications of 600V Single Conductor URD Cable

Code Name Cond.Size AWG or MCM Stranding Insulation Thickness (mls) Outside Diam (inches) Weight per 1000ft(lbs) Ampacity
Direct Burial In Duct
ALL ALUMINUM
Princeton 6 7/w 60 .298 45 90 65
Mercer 4 7/w 60 .345 64 120 85
Clemson 2 7/w 60 .403 93 155 115
Kenyon 1 19/w 80 .482 122 175 130
Harvard 1/0 19/w 80 .522 148 200 150
Yale 2/0 19/w 80 .566 179 225 170
Tufts 3/0 19/w 80 .616 217 250 195
Beloit 4/0 19/w 80 .672 265 290 225
Hofstra 250 37/w 95 .748 317 320 250
Gonzaga 300 37/w 95 .801 371 355 280
Rutgers 350 37/w 95 .851 423 385 305
Emory 500 37/w 95 .979 579 465 370
Duke 600 61/w 110 1.086 701 510 410
Furman 700 61/w 110 1.155 804 550 440
Sewanee 750 61/w 110 1.188 855 580 470
Fordham 1000 61/w 110 1.337 1109 670 545

To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Packaging: Available in 500 ft. coils 1,000ft. reels and long lengths.
The above data are approximate and subject to normal manufacturing tolerances.
Ampacity 90°C conductor temperatures, 20°C ambient temperature. RHO factor 90. 100% load factor for three conductor triplexed, 3 phase operation