All aluminum alloy stranded conductor, aslo know as aaac sorbus conductor, is mainly used for long-distance overhead lines, but also can be used as overhead line bearing line or other cable core. Mainly ASTM B399 standard, BS EN50183 standard, BS3242 standard, IEC61089 standard, French standard, DIN standard and other manufacturing standards. Our company can provide high strength aaac wire, heat resistant aluminum alloy wire, gap type wire, medium strength aluminum alloy wire and aluminum alloy core aluminum strand and other products.

| Code Name | Area | Size & Stranding of ACSR with Equal Diameter | No. & Diameter of wires | Overall Diameter | Weight | Nominal Breaking Load | Area | Stranding and Wire Diameter | Approx Overall Diameter | Weight | Nominal Breaking Load | Max.D.C. Resistance at 20℃ | |||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Nominal | Actual | Nominal | Actual | ||||||||||||
| MCM | mm2 | AWG or MCM | Al/Steel | mm | mm | kg/km | kN | AWG or MCM | mm² | mm | mm | kg/km | kN | Ω/km | |
| Akron | 30.58 | 15.48 | 6 | 6/1 | 7/1.68 | 5.04 | 42.7 | 4.92 | 6 | 13.3 | 7/1.554 | 4.67 | 37 | 4.22 | 2.5199 |
| Alton | 48.69 | 24.71 | 4 | 6/1 | 7/2.12 | 6.35 | 68 | 7.84 | 4 | 21.15 | 7/1.961 | 5.89 | 58 | 6.71 | 1.5824 |
| Ames | 77.47 | 39.22 | 2 | 6/1 | 7/2.67 | 8.02 | 108 | 12.45 | 2 | 33.63 | 7/2.474 | 7.42 | 93 | 10.68 | 0.9942 |
| Azusa | 123.3 | 62.38 | 1/0 | 6/1 | 7/3.37 | 10.11 | 172 | 18.97 | 1/0 | 53.48 | 7/3.119 | 9.36 | 148 | 16.97 | 0.6256 |
| Anaheim | 155.4 | 78.65 | 2/0 | 6/1 | 7/3.78 | 11.35 | 217 | 23.93 | 2/0 | 67.42 | 7/3.503 | 10.51 | 186 | 20.52 | 0.4959 |
| Amherst | 195.7 | 99.22 | 3/0 | 6/1 | 7/4.25 | 12.75 | 273 | 30.18 | 3/0 | 85.03 | 7/3.932 | 11.8 | 234 | 25.86 | 0.3936 |
| Alliance | 246.9 | 125.1 | 4/0 | 6/1 | 7/4.77 | 14.31 | 345 | 38.05 | 4/0 | 107.23 | 7/4.417 | 13.26 | 296 | 32.63 | 0.3119 |
| Butte | 312.8 | 158.6 | 266.8 | 26/7 | 19/3.26 | 16.3 | 437 | 48.76 | 250 | 126.66 | 19/2.913 | 14.57 | 349 | 38.93 | 0.2642 |
| Canton | 394.5 | 199.9 | 336.4 | 26/7 | 19/3.66 | 18.3 | 551 | 58.91 | 300 | 152.1 | 19/3.193 | 15.97 | 419 | 46.77 | 0.2199 |
| Cairo | 465.4 | 235.8 | 397.5 | 26/7 | 19/3.98 | 19.88 | 650 | 69.48 | 350 | 177.35 | 19/3.447 | 17.24 | 489 | 52.25 | 0.1887 |
| Darien | 559.5 | 283.5 | 477 | 26/7 | 19/4.36 | 21.79 | 781 | 83.52 | 400 | 202.71 | 19/3.686 | 18.43 | 559 | 59.74 | 0.165 |
| Elgin | 652.4 | 330.6 | 556.5 | 26/7 | 19/4.71 | 23.54 | 911 | 97.42 | 450 | 228 | 19/3.909 | 19.55 | 629 | 67.19 | 0.1467 |
| Flint | 740.8 | 375.3 | 636 | 26/7 | 37/3.59 | 25.16 | 1035 | 108.21 | 500 | 253.35 | 19/4.120 | 20.6 | 698 | 74.64 | 0.1321 |
| Greely | 927.2 | 469.8 | 795 | 26/7 | 37/4.02 | 28.14 | 1295 | 135.47 | 550 | 278.6 | 37/3.096 | 21.67 | 768 | 83.8 | 0.1202 |
| 600 | 303.8 | 37/3.233 | 22.63 | 838 | 91.38 | 0.1102 | |||||||||
| 650 | 329.25 | 37/3.366 | 23.56 | 908 | 97.94 | 0.1016 | |||||||||
| 700 | 354.55 | 37/3.493 | 24.45 | 978 | 102.2 | 0.0944 | |||||||||
| 750 | 380.2 | 37/3.617 | 25.32 | 1049 | 109.6 | 0.088 | |||||||||
| 800 | 405.15 | 37/3.734 | 26.14 | 1117 | 116.8 | 0.0826 | |||||||||
| 900 | 456.16 | 37/3.962 | 27.73 | 1258 | 131.5 | 0.0733 | |||||||||
| 1000 | 506.71 | 37/4.176 | 29.23 | 1399 | 146.1 | 0.066 | |||||||||
| Code Name | Calculated Cross Section | No..Dia.of Wires | Overall Diameter | Weight | Rated Strength |
|---|---|---|---|---|---|
| mm² | No./mm | mm | kg/km | kN | |
| Box | 18.8 | 7/1.85 | 5.55 | 51.4 | 5.55 |
| Acacia | 23.8 | 7/2.08 | 6.24 | 64.9 | 7.02 |
| Almond | 30.1 | 7/2.34 | 7.02 | 82.2 | 8.88 |
| Cedar | 35.5 | 7/2.54 | 7.62 | 96.8 | 10.46 |
| Deodar | 42.2 | 7/2.77 | 8.31 | 115.2 | 12.44 |
| Fir | 47.8 | 7/2.95 | 8.85 | 130.6 | 14.11 |
| Hazel | 59.9 | 7/3.30 | 9.90 | 163.4 | 17.66 |
| Pine | 71.6 | 7/3.61 | 10.8 | 195.6 | 21.14 |
| Holly | 84.1 | 7/3.91 | 11.7 | 229.5 | 24.79 |
| Willow | 89.7 | 7/4.04 | 12.1 | 245.0 | 26.47 |
| Oak | 118.9 | 7/4.65 | 14.0 | 324.5 | 35.07 |
| Mulberry | 150.9 | 19/3.18 | 15.9 | 414.3 | 44.52 |
| Ash | 180.7 | 19/3.48 | 17.4 | 496.1 | 53.31 |
| Elm | 211.0 | 19/3.76 | 18.8 | 579.2 | 62.24 |
| Poplar | 239.4 | 37/2.87 | 20.1 | 659.4 | 70.61 |
| Sycamore | 303.2 | 37/3.23 | 22.6 | 835.2 | 89.40 |
| Upas | 362.1 | 37/3.53 | 24.7 | 997.5 | 106.82 |
| Yew | 479.0 | 37/4.06 | 28.4 | 1319.6 | 141.31 |
| Totara | 498.1 | 37/4.14 | 29.0 | 1372.1 | 146.93 |
| Rubus | 586.9 | 61/3.50 | 31.5 | 1622.0 | 173.13 |
| Sorbus | 659.4 | 61/3.71 | 33.4 | 1822.5 | 194.53 |
| Araucaria | 821.1 | 61/4.14 | 37.3 | 2269.4 | 242.24 |
| Redwood | 996.2 | 61/4.56 | 41.0 | 2753.2 | 293.88 |
| Code Name | Nominal Area | Stranding | Diameter of Conductor | Linear Mass | Rated Strength |
|---|---|---|---|---|---|
| mm² | No./mm | mm | kg/km | kgf | |
| Box | 15 | 7/1.85 | 5.55 | 51 | 537 |
| Acacia | 20 | 7/2.08 | 6.24 | 65 | 680 |
| Almond | 25 | 7/2.34 | 7.02 | 82 | 861 |
| Cedar | 30 | 7/2.54 | 7.62 | 97 | 1014 |
| 35 | 7/2.77 | 8.31 | 115 | 1205 | |
| Fir | 40 | 7/2.95 | 8.85 | 131 | 1367 |
| Hazel | 50 | 7/3.30 | 9.9 | 164 | 1711 |
| Pine | 60 | 7/3.61 | 10.83 | 196 | 2048 |
| 70 | 7/3.91 | 11.73 | 230 | 2402 | |
| Willow | 75 | 7/4.04 | 12.12 | 245 | 2565 |
| 80 | 7/4.19 | 12.57 | 264 | 2758 | |
| 90 | 7/4.44 | 13.32 | 298 | 3112 | |
| Oak | 100 | 7/4.65 | 13.95 | 325 | 3398 |
| 100 | 19/2.82 | 14.1 | 326 | 3393 | |
| Mulberry | 125 | 19/3.18 | 15.9 | 415 | 4312 |
| Ash | 150 | 19/3.48 | 17.4 | 497 | 5164 |
| Elm | 175 | 19/3.76 | 18.8 | 580 | 6030 |
| Poplar | 200 | 37/2.87 | 20.09 | 659 | 8841 |
| 225 | 37/3.05 | 21.35 | 744 | 7724 | |
| Sycamore | 250 | 37/3.22 | 22.54 | 835 | 8664 |
| Upas | 300 | 37/3.53 | 24.71 | 997 | 10350 |
| Walnut | 350 | 37/3.81 | 26.67 | 1162 | 12053 |
| Yew | 400 | 37/4.06 | 28.42 | 1319 | 13685 |
| Totara | 425 | 37/4.14 | 28.98 | 1372 | 14233 |
| Rubus | 500 | 61/3.50 | 31.5 | 1620 | 16771 |
| Araucaria | 700 | 61/4.14 | 37.26 | 2266 | 23450 |
| Code Number | A2 Conductor | A3 Conductor | Max.D.C. Resistance of Conductor at 20℃ | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Diameter of Wires | Diameter of Conductor | Approx. Weight | Rated Strength | Number of Wires | Diameter of Wires | Diameter of Conductor | Approx. Weight | Rated Strength | ||
| mm² | No. | mm | mm | kg/km | daN | – | mm | mm | kg/km | daN | Ω/km |
| 16 | 7 | 1.83 | 5.49 | 50.4 | 5.43 | 7 | 1.84 | 5.52 | 50.8 | 6.04 | 1.7896 |
| 25 | 7 | 2.29 | 6.87 | 78.7 | 8.49 | 7 | 2.30 | 6.90 | 79.5 | 9.44 | 1.1453 |
| 40 | 7 | 2.89 | 8.67 | 125.9 | 13.58 | 7 | 2.91 | 8.73 | 127.1 | 15.1 | 0.7158 |
| 63 | 7 | 3.63 | 10.8 | 198.3 | 21.39 | 7 | 3.65 | 10.95 | 200.2 | 23.06 | 0.4545 |
| 100 | 19 | 2.78 | 13.9 | 316.3 | 33.95 | 19 | 2.79 | 13.95 | 319.3 | 37.76 | 0.2877 |
| 125 | 19 | 3.10 | 15.5 | 395.4 | 42.44 | 19 | 3.12 | 15.60 | 399.2 | 47.20 | 0.2302 |
| 160 | 19 | 3.51 | 17.55 | 506.1 | 54.32 | 19 | 3.53 | 17.65 | 511.0 | 58.56 | 0.1798 |
| 200 | 19 | 3.93 | 19.65 | 623.7 | 67.91 | 19 | 3.95 | 19.75 | 638.7 | 73.20 | 0.1439 |
| 250 | 19 | 4.39 | 21.95 | 790.8 | 84.68 | 19 | 4.41 | 22.05 | 798.4 | 91.50 | 0.1151 |
| 315 | 37 | 3.53 | 24.71 | 998.9 | 106.95 | 37 | 3.55 | 24.85 | 1008.4 | 115.29 | 0.0916 |
| 400 | 37 | 3.98 | 27.86 | 1268.4 | 135.81 | 37 | 4.00 | 28.00 | 1280.5 | 146.40 | 0.0721 |
| 450 | 37 | 4.22 | 29.54 | 1426.9 | 152.79 | 37 | 4.24 | 29.68 | 1440.5 | 164.70 | 0.0641 |
| 500 | 37 | 4.45 | 31.15 | 1585.5 | 169.76 | 37 | 4.47 | 31.29 | 1600.6 | 183.00 | 0.0577 |
| 560 | 61 | 3.67 | 33.03 | 1778.4 | 190.14 | 61 | 3.69 | 33.21 | 1795.3 | 204.95 | 0.0516 |
| 630 | 61 | 3.89 | 35.01 | 2000.7 | 213.90 | 61 | 3.91 | 35.19 | 2019.8 | 230.58 | 0.0458 |
| 710 | 61 | 4.13 | 37.17 | 2254.8 | 241.07 | 61 | 4.15 | 37.35 | 2276.2 | 259.86 | 0.0407 |
| 800 | 61 | 4.38 | 39.42 | 2540.6 | 271.62 | 61 | 4.40 | 39.60 | 2564.8 | 282.80 | 0.0361 |
| 900 | 91 | 3.81 | 41.91 | 2861.1 | 305.58 | 91 | 3.83 | 42.13 | 2888.3 | 329.40 | 0.0321 |
| 1000 | 91 | 4.01 | 44.11 | 3179.0 | 339.53 | 91 | 4.03 | 44.33 | 3209.3 | 366.00 | 0.0289 |
| 1120 | 91 | 4.25 | 46.75 | 3560.5 | 380.27 | 91 | 4.27 | 46.97 | 3594.4 | 409.92 | 0 0258 |
| 1250 | 91 | 4.49 | 49.39 | 3973.7 | 424.41 | – | – | – | – | – | – |
| Code Number | Calculated Cross Section | Number of Wires | Diameter of Wires | Overall Diameter of Conductor | Linear Mass | Rated Tensile Strength | Max.D.C. Resistance at 20℃ |
|---|---|---|---|---|---|---|---|
| mm² | mm² | No. | mm | mm | kg/km | daN | Ω/km |
| 16 | 15.89 | 7 | 1.70 | 5.1 | 43 | 444 | 2.0910 |
| 25 | 24.25 | 7 | 2.10 | 6.3 | 66 | 677 | 1.3703 |
| 35 | 34.36 | 7 | 2.50 | 7.5 | 94 | 960 | 0.9669 |
| 50 | 49.48 | 7 | 3.00 | 9.0 | 135 | 1382 | 0.6714 |
| 50 | 48.35 | 19 | 1.80 | 9.0 | 133 | 1350 | 0.6905 |
| 70 | 65.81 | 19 | 2.10 | 10.5 | 181 | 1838 | 0.5073 |
| 95 | 93.27 | 19 | 2.50 | 12.5 | 256 | 2605 | 0.3579 |
| 120 | 116.99 | 19 | 2.80 | 14.0 | 322 | 3268 | 0.2854 |
| 150 | 147.11 | 37 | 2.25 | 15.8 | 406 | 4109 | 0.2274 |
| 185 | 181.62 | 37 | 2.50 | 17.5 | 500 | 5073 | 0.1842 |
| 240 | 242.54 | 61 | 2.25 | 20.3 | 670 | 6774 | 0.1383 |
| 300 | 299.43 | 61 | 2.50 | 22.5 | 827 | 8363 | 0.1120 |
| 400 | 400.14 | 61 | 2.89 | 26.0 | 1104 | 11176 | 0.0838 |
| 500 | 499.63 | 61 | 3.23 | 29.1 | 1379 | 13960 | 0.06709 |
| 625 | 626.20 | 91 | 2.96 | 32.6 | 1732 | 17490 | 0.0540 |
| 800 | 802.09 | 91 | 3.35 | 36.9 | 2218 | 22402 | 0.0418 |
| 1000 | 999.71 | 91 | 3.74 | 41.1 | 2767 | 27922 | 0.0335 |