    MV Aerial Bundled Cables are suitable for aerial installation and for public power distribution networks with rated voltages of 6/10 Up to and including 18/30 KV, Fixed for pylons, clamped to tunnel walls , etc.

    STANDARD

    Basic design to IEC 60502 standard

    Application

    Aerial bundled cables are mainly used for secondary overhead lines on poles or as feedes to residential premises. 

    Construction

    Phase Conductor: Circular compacted stranded H68 aluminium to BS2627. Conductor Screen: Extruded semi-conductive layer. Insulation: XLPE. Insulation Screen: Extruded semi-conductive layer. Metallic Screen(optional): Copper wire screen or copper tape screen. Separator: Semi-conductive swellable tape. outer Sheath: HDPE. Support Conductor: Galvanized steel wires. Assembly: Three XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay.

    Technical Parameter

    Number of Cores Phase Conductor Messenger Suspension Unit Continuous
    xNominal Stranding Nominal Maximum Stranding Nominal   current rating
    Cross Section Sectional Conductor Sectional Breaking at 300℃
      Area Resistance Area Load ambient temp
    No.xmm2 No.xmm mm2 Ω/Km No.×mm mm² KN A
    3X50 + 1X25 19/1.78 50 0.641 7/3.0 50 60 116
    3X70 + 1X50 19/.14 70 0.443 7/3.15 50 62 210
    3X95+ 1X50 19/2.52 95 0.32 7/3.0 50 60 173
    3X185+1X120 37/2.52 185 0.164 7/4.67 120 150 259
    3X150 +1X50 37/2.25 150 0.206 7/3.15 50 62 365
    3X240 +1X50 61/2.25 240 0.125 7/3.15 50 62 500

    IEC 60502 6.35/11kV ABC for Overhead Distribution Lin
    Other cross-sections can be offered upon request. IEC 60502 19/33 kV ABC for Overhead Distribution Lines

    Number of Cores Phase Conductor Messenger Suspension Unit Continuous
    xNominal Stranding Nominal Maximum Stranding Nominal   current rating
    Cross Section Sectional Conductor Sectional Breaking at 300℃
      Area Resistance Area Load ambient temp
    No.xmm2 No.xmm mm2 Ω/Km No.×mm mm² KN A
    3X50 + 1X50 19/1.78 50 0.641 7/3.0 50 60 165
    3X150+ 1X50 37/2.25 150 0.206 7/3.0 50 60 315
    3X185+1X70 37/2.52 185 0.164 7/3.57 70 91 355
    3X70 +1X50 19/2.14 7 0.443 7/3.15 50 62 250
    3X150 +1X50 37/2.25 150 0.206 7/3.15 50 62 370

    Other cross-sections can be offered upon request.

     