    Directly buried or installed in ducts for 600 volt secondary distribution.

    STANDARD

    ASTM B-230,B-231 and ICEA S-66-524 ,UL Standard 854 for type USE

    Application

    600V Single Conductor URD Cable is designed for use in secondary distribution circuits, where installed in duct or direct burial applications. Maximum operating temperature is not to exceed 90°C in wet and dry locations. Voltage rating is 600 volts. As an option, this cable can provided pre-pulled into duct.

    Construction

    Concentric stranded or compressed 1350-H19 aluminum conductor, crosslinked polyethylene insulation.

    Cable in Duct(CIC)

    Abrasion Resistant

    Technical Parameter

    Code Name Cond.Size AWG or MCM Stranding Insulation Thickness (mls) Outside Diam (inches) Weight per 1000ft(lbs) Ampacity
    Direct Burial In Duct
    ALL ALUMINUM
    Princeton 6 7/w 60 .298 45 90 65
    Mercer 4 7/w 60 .345 64 120 85
    Clemson 2 7/w 60 .403 93 155 115
    Kenyon 1 19/w 80 .482 122 175 130
    Harvard 1/0 19/w 80 .522 148 200 150
    Yale 2/0 19/w 80 .566 179 225 170
    Tufts 3/0 19/w 80 .616 217 250 195
    Beloit 4/0 19/w 80 .672 265 290 225
    Hofstra 250 37/w 95 .748 317 320 250
    Gonzaga 300 37/w 95 .801 371 355 280
    Rutgers 350 37/w 95 .851 423 385 305
    Emory 500 37/w 95 .979 579 465 370
    Duke 600 61/w 110 1.086 701 510 410
    Furman 700 61/w 110 1.155 804 550 440
    Sewanee 750 61/w 110 1.188 855 580 470
    Fordham 1000 61/w 110 1.337 1109 670 545

    To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
    Packaging: Available in 500 ft.coils 1,000ft. reels and long lengths.
    The above data are approximate and subject to normal manufacturing tolerances.
    Ampacity 90°C conductor temperatures, 20°C ambient temperature. RHO factor 90. 100% load factor for three conductor triplexed, 3 phase operation

     